- Location: Glasgow
- Client: Rosehill Housing
- Services: Technical Survey & Options Appraisal
Technical Assessment & Review
The client’s preference is for the services were both environmentally friendly (low carbon), reliable, and comfortable.
We applied the IES model to calculate the heat demands of the site, including building fabric heat losses, ventilation heat losses, domestic hot water demands, system losses, and thermal response. These calculations were adjusted to account for heat gains from occupancy, equipment, lighting, and solar energy. This allowed us to model the building’s thermal requirements based on internal heat settings and local outside temperature data for a year.
Once we confirmed the heat load, we used our extensive database and experience to estimate the financial and operational costs for each available option. These cost projections are presented over the expected 20-year lifespan of the equipment.
Read More
Read More
Dynamic Thermal Analysis
We created a detailed thermal model of the property using IES-VE, capable of running simulations at a 10-minute resolution for accurate performance replication.
This model optimizes the utilization of solar thermal energy by storing daily contributions for evening or next-day use.
Ensuring the model’s accuracy and level of detail is crucial as it profoundly impacts the quality of the results. Inaccurate output can disrupt subsequent work.
Heat Load Modelling and Overheating
Traditional ‘steady state’ calculations for heat load tend to oversize the heating plant requirement as they are limited in their assumed internal and external parameters. These simple calculations also cannot take account the previous operating periods.
In simpler terms, the building might retain some heat from the previous day instead of assuming it starts completely cold each day. It could also absorb heat from solar energy during the day and gradually release it into the rooms overnight.
Utilizing the IES model we were able to produce comprehensive calculations culminated in the determination of both the annual net thermal demand and the design day heat load.
With climate change, overheat risk in modern buildings is on the rise and is likely to become a more significant concern. You can assess the likelihood of high internal temperatures during hot weather using the SAP method. In Scotland, if the building can be cross-ventilated (with windows open at least 50% of the time at either end of the building) on hot days/nights, the overheat risk is considered “not significant.” If windows cannot be opened, you should consider mitigation measures such as screens, blinds, and/or air conditioning.
Heating Selection
In practice the main heating systems are heat pumps, gas/oil boilers and electrical heaters (either point source or direct wet system). There is a gas link available, based on the location of the site.
The options for heating in this case were:
- ASHP for each dwelling
- Mini ‘ambient heat pump’ in dwelling and communal gas boiler
- Electrical Radiators & Immersion (for DHW)
- Electrical Radiators & mini air heat pump (for DHW)
- Gas combi boiler.
Finally, there is an Eco incentive for heat pumps (ASHP, GSHP) and solar thermal, but we ran the financials without that subsidy as it can be difficult to go for